Mitsubishi Electric QJ71GF11-T2 User Manual page 461

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

Error code
DAD0
to DAD4
Network module failure
H
H
DAE0
to DAE3
Network module failure
H
H
DAE4
CPU module failure
H
DAE5
Network module failure
H
CC-Link IE Field not supported by the
DAE6
H
CPU
DAE7
Network module failure
H
DAE8
Switch setting information error
H
UINI instruction execution disabled
DAE9
(the CPU module not supporting the
H
function)
DAF1
Network module failure
H
DAF2
Flash ROM failure
H
Error
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• Execute hardware and self-loopback tests.
• If this error persists, please consult your local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• Use a CPU module compatible with the master/local module.
• If this error persists, please consult your local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• When using the CCPASET instruction or the C Controller module, check
the intelligent function module switch setting, and write the setting data to
the CPU module again.
• When not using the CCPASET instruction or the C Controller module,
clear the intelligent function module switch setting, and write the setting
data to the CPU module again.
• Check the serial number (first five digits) of the master/local module to
check if the module supports the function. Then correct the settings in the
network parameter window.
• If this error persists, please consult your local Mitsubishi representative.
Check the serial number (first five digits) of the CPU module to check if the
module supports the function. If not, replace the module with the one with
the latest version.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• The flash ROM may be faulty. Check the wire and cable distances and
grounding condition of each device, and take measures against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
CHAPTER 12 TROUBLESHOOTING
Action
12
459