(11)Checking the station number setting status of the own station

The station number setting status of the own station can be checked in the CC-Link IE Field Network diagnostics.
It can be also checked using link special relays (SBs) and a link special register (SW).
(a) Setting the station number in the network parameter window of GX Works2
1.
Setting the station number turns off Station number setting status of the own station (SB0046) and
Station number status of the operating station (SB004F).
2.
The station number of the own station is stored in Station number (SW0042).
(b) Setting the station number using the UINI instruction
1.
When the module is powered on, the station number is not set. Therefore, Station number setting
status of the own station (SB0046) turns on. Station number status of the operating station
(SB004F) also turns on.
2.
FF
is stored in Station number (SW0042).
H
3.
Executing the UINI instruction to set the station number turns off Station number setting status of
the own station (SB0046).
4.
The station number of the own station is stored in Station number (SW0042).
Number
SB0046
Station number setting status of the own station
SB004F
Station number status of the operating station

(12)Dedicated instructions

The following link special relays (SBs) and link special registers (SWs) are used for dedicated instructions.
(
Page 236, CHAPTER 10)
(a) RECV instruction (
1.
When data are stored in the own station channel area, the corresponding RECV execution request
flag (SB0030 and SB0031) turns on.
Use the flag as a start contact and execute the RECV instruction.
After the completion of the RECV instruction, the flag is turned off.
Number
SB0030
RECV execution request flag (1)
SB0031
RECV execution request flag (2)
SB0047
Baton pass status (own station)
Description
Page 294, Section 10.9)
Description
Number
SW0042
Station number
Number
CHAPTER 11 PROGRAMMING