Mitsubishi Electric QJ71GF11-T2 User Manual page 445

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

Error code
Invalid number of relays in transient
D207
H
transmission
Network No. error in transient
D208
H
transmission
Target station No. error in transient
D209
H
transmission
Target station No. error in transient
D20A
H
transmission
Specified master station No. error in
D20B
H
transient transmission
Current master station No. error in
D20C
H
transient transmission
Transient data transmission
D20D
H
completion wait timeout
Header information error in transient
D20E
H
transmission
Target station No. error in transient
D20F
H
transmission
Target station No. error in transient
D210
H
transmission
Own station No. not set (dedicated
D211
H
instruction)
D212
Transient transmission failed
H
D213
Transient data command error
H
D214
Transient data length error
H
D215
Transient data request error
H
D216
and D217
Transient data command error
H
H
Incorrect number of read/write
D218
H
transient data
D219
Transient data attribute code error
H
D21A
Transient data access code error
H
Error
• Change the system configuration so that the number of relay stations may
be seven or less.
• Check if the routing parameters are correctly set.
• When the IP communication test is executed, change the IP address in
the "Communication Target" so that the number of relay stations may be
127 or less.
• Correct the network number at the request source, and retry the
operation.
• If the request source is on another network, check if the routing
parameters are correctly set.
Correct the target station number at the request source, and retry the
operation.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• When the own station, target station, or relay station detected an error,
identify the cause of the error and take action.
• Reduce the frequency of transient transmission, and retry the operation.
• When the mode of the master station (submaster station) is "Online (High
Speed Mode)", change it to "Online (Normal Mode)" and retry the
operation.
• Check if the switching hub and the cables at the request source are
connected properly.
Correct the header information at the request source, and retry the
operation.
Check that the command can be requested to all or a group of stations at the
request source, and retry the operation.
Correct the header information at the request source, and retry the
operation.
Set the station number in the parameter setting, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• Connect the cable to the other port on the request source, and retry the
operation.
• Reduce the frequency of transient transmission, and retry the operation.
• Correct the request command at the request source, and retry the
operation.
• Check the first five digits of the serial number of the master/local module.
If the module does not support the used function, replace it with the
module with the latest version.
Correct the data length at the request source, and retry the operation.
Change the mode to Online, and retry the operation.
Correct the request command at the request source, and retry the operation.
Correct the number of read/write device data at the request source, and retry
the operation.
Correct the attribute code at the request source, and retry the operation.
Correct the access code at the request source, and retry the operation.
CHAPTER 12 TROUBLESHOOTING
Action
12
443