(2) Checking method
To check whether routing parameters have been correctly set and transient transmission can be performed,
perform a communication test from CC-Link IE Field Network diagnostics. (
(3) Precautions
(a) Different control CPUs are set to the network modules on a relay station in a
multiple CPU system
Set the same routing parameters to all the control CPUs.
(b) When multiple master/local modules with the same network number are connected
to one system
Set the station number of a module with the smallest slot number in "Relay Station No.".
In a multiple CPU system, set the station number of a module with the smallest slot number, regardless of the
CPU number of the control CPU.
Station
No.0
1
2
1
1
2
2
Set the same routing parameters.
Network No.1
Station
Station
CPU
module
No.1
No.2
Slot No.
0
1
Set "1" in "Relay Station No.".
CHAPTER 7 PARAMETER SETTING
Page 79, Section 6.4.3)
Control CPU setting
Network No.2
Station
Station
No.3
No.0
2
7
121