(d) CCPASET instruction setting
• Control data
Device
(S1)+0
D2000
(S1)+1
D2001
(S1)+2
D2002
(S1)+3
D2003
(S1)+4 and
D2004 and
(S1)+5
D2005
• Network configuration setting data
Device
(S2)+0
D2010
(S2)+1
D2011
(S2)+2
D2012
(S2)+3
D2013
(S2)+4
D2014
(S2)+5
D2015
(S2)+6
D2016
(S2)+7
D2017
(S2)+8
D2018
(S2)+9
D2019
(S2)+10
D2020
(S2)+11
D2021
(S2)+12
D2022
(S2)+13
D2023
(S2)+14
D2024
• Reserved station specification data
Device
(S3)+0
D2610
(S3)+1 to
D2611 to
(S3)+7
D2617
372
Item
Completion status
Setting flag
Total number of slave stations
Constant link scan time
IP address (network address)
Item
Slave station setting
information
RX/RY offset
1st station
RX/RY size
RWr/RWw offset
RWr/RWw size
Slave station setting
information
2nd
RX/RY offset
station
RX/RY size
RWr/RWw offset
RWr/RWw size
Slave station setting
information
RX/RY offset
3rd station
RX/RY size
RWr/RWw offset
RWr/RWw size
Item
Reserved station specification
Setting value
(The system sets this item.)
0107
H
Network configuration settings: Valid
• Reserved station specification: Valid
• Error invalid station setting: Valid
• Submaster function: Invalid
• IP packet transfer function: Disable
• Data link faulty station setting: Hold
• Output setting during CPU STOP: Hold
• Link scan mode setting: Asynchronous
• Loopback function setting: Not used
3
0: (No setting)
0 (No setting)
Setting value
2101
H
• Station type: Intelligent device station
• Station No.: 1
0
H
32 points
0
H
16 points
2102
H
• Station type: Intelligent device station
• Station No.: 2
20
H
32 points
10
H
16 points
2103
H
• Station type: Intelligent device station
• Station No.: 3
40
H
32 points
20
H
16 points
Setting value
4
(The station number 3 is set as a reserved station.)
H
No setting