Mitsubishi Electric QJ71GF11-T2 User Manual page 486

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

Number
Name
Data link status (each
SB00B0
station)
Data link status
SB00B1
(master station)
Network connection
SB00B8
status (each station)
Data link status (station
SB00BF
No.0)
Reserved station
SB00C0
setting status
484
Description
Stores the cyclic transmission status for each station.
OFF: Cyclic transmission for all stations in progress
ON: Cyclic transmission not executed for some stations
If cyclic transmission are not executed for some stations, the status of
each station can be checked by Data link status (each station) (SW00B0
to SW00B7).
Depending on the timing of the link refresh, the update of Data link status
(each station) (SW00B0 to SW00B7) may be offset by one sequence
scan.
(Conditions)
• This is enabled when Baton pass status (own station) (SB0047) is off.
• Reserved stations and stations higher than the maximum station No.
are ignored.
Stores the data link status of the master station (master operating
station).
OFF: Normal
ON: Error
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Stores if any network connection station is found.
OFF: No network connection station
ON: Network connection station found
If a network connection station is found, the status of each station can be
checked using Network connection status (SW00B8 to SW00BF).
Depending on the timing of the link refresh, the update of Network
connection status (SW00B8 to SW00BF) may be offset by one sequence
scan.
Stores the data link status of the station number 0.
OFF: Normal
ON: Error
(Condition)
• This is enabled when the submaster function is used.
Stores if a reserved station has been set.
OFF: No setting
ON: Set
When a reserved station has been set, each station status can be
checked using Reserved station setting status (SW00C0 to SW00C7).
Depending on the timing of the link refresh, the update of Reserved
station setting status (SW00C0 to SW00C7) may be offset by one
sequence scan.
(Condition)
• This is enabled when Baton pass status (own station) (SB0047) is off.
Availability
Master
station
Local
(submaster
station
station)