Item
Assign RWw/RWr points in increments of 4. (
When "Sub-Master Station" is selected in "Station Type", points can also be
assigned for the master station. (
RWw/RWr Setting
To equally assign points or the same points, go to [Equal Assignment] or
[Identical Point Assignment] under [CC IE Field Configuration].
(
Page 95, Section 7.3 (1) (d))
Link refresh target devices in the CPU module are displayed for each link
device of the master/local module.
Refresh Device
Target devices are displayed when refresh parameters have been set.
(
Page 103, Section 7.5)
Set this item to reserve the slave station or to set the slave station as an
error invalid station. (
This item cannot be set for the submaster station.
• No Setting
The slave station is connected to the network.
Reserved/Error
• Reserved Station
Invalid Station
The slave station is reserved for future expansion. By reserving a slave
station, link device assignment will not change even if the slave station is
added or the reservation is cancelled. Therefore, the program needs not
to be modified. Physical connection of the slave station is not required.
• Error Invalid Station
Even if a slave station is disconnected during data link, the master station
will not detect the slave station as a faulty station.
Enter the name of a device if required.
The name entered is displayed in "Network Status" of the CC-Link IE Field
diagnostics.
Alias
However, even if the name of the extension module connected to the
remote device station is entered, the name is not displayed in the CC-Link
IE Field diagnostics.
Information entered in "Comment1" on the "Property" window displayed by
Comment
right-clicking on the module in "List of stations" or "Configuration of the
devices" is displayed.
Station-specific
Set the station-specific mode of the slave station. This setting is available
mode setting
only when the slave station supports the station-specific mode.
The slave stations are listed. Drag and drop the modules from "Module List"
Module List
to the station list area or the device map area to set the information of the
slave stations into the master station.
(b) Change Transmission Path Method
[CC IE Field Configuration]
Description
Page 124, Section 8.1.1)
Page 180, Section 8.8)
Page 176, Section 8.5)

[Change Transmission Path Method]

CHAPTER 7 PARAMETER SETTING
Setting range
• Points:
Setting
Station Type
range
Master Station, Local
Station, Intelligent
4 to 1024
Device Station, Sub-
Master Station
Remote Device Station
4 to 64
Cannot be
Remote I/O Station
set.
• Device number: 0 to 1FFF
H
(Default: varies depending on the set
module)
• No Setting
• Reserved Station
• Error Invalid Station
(Default: No Setting)
Up to 8 characters
(Default: Blank)
Up to 32 characters
(Default: Blank)
The setting varies depending on the
set module.
7
91