(b) Cyclic transmission stop/restart (own station)
(Cyclic transmission stop)
1.
Turn on Link stop (own station) (SB0001).
2.
When the master/local module accepts the request, Link stop request accept status (own station)
(SB0052) turns on.
3.
When cyclic transmission stop is completed, Link stop completion status (own station) (SB0053)
turns on.
4.
If cyclic transmission is stopped with error, an error code will be stored in Data link stop status
(own station) (SW0051).
5.
Turn off Link stop (own station) (SB0001).
(Cyclic transmission restart)
6.
Turn on Link start (own station) (SB0000).
7.
When the master/local module accepts the request, Link start request accept status (own station)
(SB0050) turns on.
8.
When cyclic transmission restart is completed, Link start completion status (own station)
(SB0051) turns on.
9.
If the cyclic transmission is restarted with error, an error code will be stored in Data link start
status (own station) (SW0050).
10.
Turn off Link start (own station) (SB0000).
Number
SB0000
Link start (own station)
SB0001
Link stop (own station)
SB0050
Link start request accept status (own station)
SB0051
Link start completion status (own station)
SB0052
Link stop request accept status (own station)
SB0053
Link stop completion status (own station)
410
Description
Number
SW0050
Data link start status (own station)
SW0051
Data link stop status (own station)
Description