(a) Control data
Device
Item
Execution/
(S1)+0
abnormal end type
Setting data
b15
to
0
1) Execution type (bit 0)
0: Without arrival confirmation
When the target station is on the same network
The process is completed when data is sent from the own
station.
Request
source
Completed
When the target station is on another network
The process is completed when data arrives at the relay station
on the same network.
Request
Relay
source
station
Completed
1: With arrival confirmation
The process is completed when data is written in the target
station.
Request
Relay
source
station
Completed
Target
station
When "0: Without arrival confirmation" is specified, the result is
regarded as normal on the own station even if the writing to the target
station fails, as follows.
• When communication ends normally even though sent data are
abnormal
• When data cannot be written to the target station, because
instructions are executed to the same station from multiple stations
(The target station generates an error code (D202
2) Abnormal end type (bit 7)
Specify the data set status in case of abnormal end.
0: After (S1)+11, no data is set for abnormal end.
1: Data at the time of abnormal end is set in the area starting from
(S1)+11.
CHAPTER 10 DEDICATED INSTRUCTIONS
b7
to
b0
2
0
1
Target
station
Target
station
Completed
Target
station
or D282
))
H
H
Setting range
Set by
0000
H
0001
H
User
0080
H
0081
H
265
10