Error code
UINI instruction execution disabled
D636
(instruction executed to a station other
H
than a local station)
UINI instruction execution disabled
D637
(the station number already set using
H
the parameter)
UINI instruction execution disabled
D638
H
(the station number already in use)
UINI instruction execution disabled
D639
(the station number already set using
H
the UINI instruction)
UINI instruction execution disabled
D63A
(the CPU module not supporting the
H
function)
Parameter error (submaster station
D63C
H
setting address error)
Parameter error (reserved station
D63D
H
setting error)
Parameter error (error invalid station
D63E
H
setting error)
Parameter error (IP packet transfer
D640
H
address setting error)
D641
Parameter error (IP address error)
H
Parameter error (network parameter
D642
H
mismatch)
Parameter error (network
D643
H
configuration settings mismatch)
Parameter error (supplementary
D644
H
setting mismatch)
Parameter error (mode setting
D645
H
mismatch)
454
Error
Use one of the following methods and execute the UINI instruction to the
local station again.
• Select the local station for the station type in the network parameter
window of GX Works2.
• Set 31FF
• Check if the master/local module specified in the argument of the UINI
instruction is the local station.
Use one of the following methods to execute the UINI instruction again with
the station number not set.
• Select "Specify Station No. by Program" in the network parameter window
of GX Works2.
• Set 31FF
Correct the station number to be set using the UINI instruction to the station
number not used for other stations. Then execute the UINI instruction again.
Reset the CPU module or power on the system again to clear the station
number. Then execute the UINI instruction again.
Check the serial number (first five digits) of the CPU module to check if the
module supports the function. If not, replace the module with the one with
the latest version.
• Write the network parameters to the CPU module again.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Cancel the reserved station setting configured for the submaster station in
the network configuration settings.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Cancel the error invalid station setting configured for the submaster
station in the network configuration settings.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the value in the IP address (setting data) and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the parameters set for the submaster station so that they will be
the same as those set for the master station and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the parameters set for the submaster station so that they will be
the same as those set for the master station and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the parameters set for the submaster station so that they will be
the same as those set for the master station and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the mode set for the submaster station so that it will be the same
as that set for the master station and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
Action
for Switch 2 in the intelligent function module switch setting.
H
for Switch 2 in the intelligent function module switch setting.
H