10.17

GP.CCPASET (Setting Parameters)

This instruction sets parameters to the master/local module.
Usually, the parameters of the master/local module are set using the network parameters in GX Works2. In the
following applications, they are set using the CCPASET instruction.
• To change the parameter settings without resetting the CPU module
• To mount more master/local modules than the number of modules that can be set using GX Works2
10.17.1
Procedure for setting parameters using the CCPASET
instruction
(1) Procedure
Before setting parameters using the CCPASET instruction, set the network No. of the master/local module using
the intelligent function module switch setting.
1.
Open the "I/O Assignment" tab of GX Works2.
Project window
2.
Add the master/local module under "I/O Assignment".
3.
Click the
4.
Enter values for "Switch 1" to "Switch 5".
[Parameter]
[PLC Parameter]
button.
CHAPTER 10 DEDICATED INSTRUCTIONS
"I/O Assignment" tab
10
359