Input Status Of Data Link Faulty Station; Cyclic Data Output When A Stop Error Occurs In The Cpu Module; When Data Link Is Stopped By Users; Setting On A Station With A Data Link Error - Mitsubishi Electric QJ71GF11-T2 User Manual

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

(1) Setting method
(a) Input status of data link faulty station
Set this item in the "Network Operation Settings" window. (
(b) Cyclic data output when a stop error occurs in the CPU module
Select "PLC Parameter" and set it in "Intelligent Function Module Detailed Setting".
[Project Window]
button
(2) Precautions
(a) When data link is stopped by users
When cyclic transmission is stopped using one of the following methods, the input status of the faulty station is
held.
• CC-Link IE Field Network diagnostics (
• Link special relay (SB), link special register (SW) (
(b) Setting on a station with a data link error
When the following settings are set to "Hold" on the station where a data link error has occurred, the input
status of the own station upon error is held, regardless of setting.
• "Network Operating Settings"
• "PLC Parameter"
(
Page 139, Section 8.1.6 (1) (b))
[Parameter]
[PLC Parameter]
"Error Time Output Mode"
Page 221, Section 9.4)
"Output Setting During CPU STOP" (
"Intelligent Function Module Detailed Setting"
CHAPTER 8 FUNCTIONS
Page 101, Section 7.4)
"I/O Assignment" tab
Page 408, Section 11.4 (1))
Page 141, Section 8.1.7 (2))
"Error Time Output Mode"
8
141