(4) Program example (parameter setting in the master station)

A program example is described below. The program sets parameters to the master station of network number 1
when M171 turns on.
(a) System configuration
The following figure shows a system configuration to set CC-Link IE Field Network parameters for the master
station.
CPU module
CCPASET instruction
execution source
(own station)
Device
(no actual device connected)
Intelligent device station (Station No.3)
(b) Intelligent function module switch setting
Before executing the CCPASET instruction, set the intelligent function module switches as follows.
Project window
button.
(c) Devices used in the program
Device
M171
Start contact
M172
Completion device
M173
Completion status indication device
D2000 to
Control data
D2003
Master station (station No.0)
Master/local module
Parameter settings
Reserved station
[Parameter]
[PLC Parameter]
Description
CHAPTER 10 DEDICATED INSTRUCTIONS
Intelligent device station (station No.1)
Network No.1
Intelligent device station (station No.2)
"I/O Assignment" tab
Device
D2010 to
Network configuration setting data
D2024
D2610 to
Reserved station specification data
D2617
D2620 to
Error invalid station setting data
D2627
Press the
Description
371