(2) Function
(a) REMTO instruction overview
The instruction writes data by the specified number of words (n5) from the own station start device (S) into the
buffer memory (after (n4)) of the intelligent device station/remote device station.
Specify the target stations in setting data ("Jn"/Jn), (n2), and (n3).
When the writing of data is completed, the completion device (D) turns on.
[Own station]
CPU module
(S)
REMTO
(b) Target stations that can be specified
For details on target stations which can be specified, refer to the following.
Page 236, Section 10.1 (1)
(c) Checking the execution status of the REMTO instruction
The execution status (completion or error) of the REMTO instruction can be checked using the following
devices specified in the setting data.
• Completion device (D)
This device turns on in the END process of the scan where the REMTO instruction is completed and turns
off in the next END process.
• Completion status indication device ((D)+1)
If the REMTO instruction fails, this device turns on in the END process of the scan where the REMTO
instruction is completed and turns off in the next END process.
[Target station]
Master/local
Head module
module
Channel 1
Channel n
Channel 32
CHAPTER 10 DEDICATED INSTRUCTIONS
Intelligent function
module
n4
n5
words