Error code
Parameter error (loopback setting
D626
H
error)
Parameter error (slave station setting
D627
H
information error)
D628
Parameter error (station type error)
H
Parameter error (Station No. range
D629
H
error)
Parameter error (data link faulty
D62A
H
station setting error)
Parameter error (output status setting
D62B
H
for a CPU STOP error)
Parameter error (interrupt setting
D62C
H
error)
D62D
Data link start failed
H
Execution error at the local station
D630
H
(CCPASET)
Parameter error (incorrect number of
D634
H
submaster stations)
Parameter error (incorrect submaster
D635
H
station number)
Error
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the value in the total number of slave stations (setting data), and
retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Change the station number in the setting data to any of 1 to 120, and retry
the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the output status setting for CPU STOP, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the output status setting for CPU STOP, and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Correct the interrupt settings and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
Data link start failed due to any of the following causes. Remove the error
cause, and retry the operation.
• Station No. not set
• CPU module error on the own station
• More than one master station or submaster station exists.
• Station type mismatch
• Master station lost
• Own station No. out of range
• Station No. already in use (own station)
• Own station reserved
• Parameter error
• Parameter communication in progress
• Parameters not received (master station only and no slave station exists)
• Link stop command
Configure the network number, station type, and station number in the
switch setting.
Then execute the instruction again with the network parameter not set.
• Write the network parameters to the CPU module again.
• Set one submaster station in the station type set for each station and retry
the operation.
• If this error persists, please consult your local Mitsubishi representative.
• Write the network parameters to the CPU module again.
• Set the station number within 1 to 120 and retry the operation.
• If this error persists, please consult your local Mitsubishi representative.
CHAPTER 12 TROUBLESHOOTING
Action
12
453