Parameter Set Flag (Buffer Memory Address: 31740 (7Bfc H)); Switch Setting Parameter Check Result (Buffer Memory Address: 31741 (7Bfd H)); Parameter Communication Result (Buffer Memory Address: 31742 (7Bfe H)); Setting Flag (Buffer Memory Address: 31743 (7Bff H)) - Mitsubishi Electric QJ71GF11-T2 User Manual

Melsec-q series cc-link ie field network master/ local module
Table of Contents

Advertisement

(c) Parameter set flag (buffer memory address: 31740 (7BFC
Data stored to this buffer memory indicates completion of parameter setting, sends a cyclic start request, and
stores the results of these two operations.
Also, the buffer memory stores the results of the commands above.
• 00
: Initial/idle status (stored by the system)
H
• 01
: Parameter setting ended (stored by the user)
H
• 02
: Parameter communication completed (stored by the system)
H
• 03
: Cyclic start being requested (stored by the user)
H
• FE
: Parameter communication failed (stored by the system)
H
• FF
: Cyclic start completed (stored by the system)
H
(d) Switch setting parameter check result (buffer memory address: 31741 (7BFD
This buffer memory stores the results of the switch setting parameter check.
• 0: Normal
• 1 or greater: Error (error code)
(e) Parameter communication result (buffer memory address: 31742 (7BFE
This buffer memory stores the result of parameter communications between the C Controller module and the
master/local module.
• 0: Normal
• 1 or greater: Error (error code)
(f) Setting flag (buffer memory address: 31743 (7BFF
• For the master station and the submaster station
Bit
b0
b1
b2
b3
b4 and b5
b8
b9
b11
Use b0 to b2 to set whether to enable each setting data.
Storing "0: Invalid" will operate the station with the default of the parameter. (
Use b3 to set whether to enable the submaster function.
Use b4 and b5 to set whether to enable the IP packet transfer function.
Use b8, b9, and b11 to configure the network operation settings.
540
b15 to
b12
b11
b10
b9
Fixed to 0
Network configuration setting data
Reserved station specification data
Error invalid station setting data
Submaster function
IP packet transfer function
Data link faulty station setting
Output setting during CPU STOP
Loopback function setting
b8
b7
to
b6
b5
b4
b3
Fixed to 0
Item
))
H
))
H
b2
b1
b0
Setting
0: Invalid
1: Valid
b5
Fixed to 0.
0: Disable
1: Enable
0: Clear
1: Hold
0: Hold
1: Clear
0: Not used
1: Used
Page 81, CHAPTER 7)
))
H
))
H
b4