Error code
D0E3
Own station No. out of range
H
Multiple master stations (including own
D0E4
H
station)
Multiple submaster stations (including
D0E5
H
own station)
D0F0
Network module failure
H
D100
and D101
Network module failure
H
H
D110
to D113
Network module failure
H
H
D200
Transient data received twice
H
Header information error in transient
D201
H
transmission
D202
Send buffer full
H
Read/write address error in transient
D203
H
transmission
Network No. error in transient
D204
H
transmission
Target station No. error in transient
D205
H
transmission
Network No. error in transient
D206
H
transmission
442
Error
Add the station information of the own station in the network configuration
settings of the master station (submaster station).
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• After taking the above actions, power off and on all the stations where this
error has been detected or reset them.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• After taking the above actions, power off and on all the stations where this
error has been detected or reset them.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• Check if the cables and the switching hub are connected properly.
• If the request source resides in another network, check if the routing
parameters are correctly set, and take corrective action.
Correct the header information at the request source, and retry the
operation.
• Reduce the frequency of transient transmission, and retry the operation.
• When the mode of the master station (submaster station) is "Online (High
Speed Mode)", change it to "Online (Normal Mode)" and retry the
operation.
• Check if the cables and the switching hub are connected properly.
Correct the read/write address at the request source, and retry the
operation.
• Correct the network number at the request source, and retry the
operation.
• If the request source is on another network, check if the routing
parameters are correctly set.
Correct the target station number at the request source, and retry the
operation.
• Correct the network number at the request source, and retry the
operation.
• If the request source is on another network, check if the routing
parameters are correctly set.
Action