Error code
Submaster setting error (buffer
D82C
H
memory start parameter area)
Submaster setting error (buffer
D82D
H
memory start parameter area)
IP packet transfer function not
D82E
H
supported (IP communication test)
D902
Incorrect online test data
H
D903
Communication test retry error
H
Communication monitoring timeout in
D905
H
communication test
Communication test transmission
D906
H
completion wait timeout
Header information error in transient
D909
H
transmission
Communication test data received
D90A
H
twice
D90B
Incorrect number of stations
H
Invalid communication test target
D90C
H
station
D90D
Cable test retry error
H
IP packet transfer function not
D90E
H
supported
D90F
IP communication test in progress
H
D910
IP address not set (own station)
H
D911
Destination IP address error
H
DA00
and
H
Network module failure
DA01
H
DA10
to DA18
Network module failure
H
H
458
Error
Do not set a submaster station number in the reserved station specification
in the buffer memory start parameter area.
Do not set a submaster station number in the error invalid station setting in
the buffer memory start parameter area.
Check the first five digits of the serial number of the CPU module.
If the module does not support the used function, replace it with the CPU
module with the latest version.
• Correct the data at the station that started the online test, and retry the
operation.
• If this error persists, please consult your local Mitsubishi representative.
After completion of the communication test, retry the operation.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool, take action, and retry the operation.
• Check if the routing parameters are correctly set.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool, take action, and retry the operation.
• Reduce the frequency of transient transmission, and retry the operation.
• When the mode of the master station (submaster station) is "Online (High
Speed Mode)", change it to "Online (Normal Mode)" and retry the
operation.
• Check if the routing parameters are correctly set.
Check the network status using the CC-Link IE Field Network diagnostics of
the programming tool, take action, and retry the operation.
Check the network status using the CC-Link IE Field Network diagnostics of
the programming tool, take action, and retry the operation.
• Check the network status using the CC-Link IE Field Network diagnostics
of the programming tool.
• If the number of slave stations (including a submaster station) per network
is more than 120, reduce it to 120 or less.
• Correct the "Target Station" setting in the "Communication Test" window,
and retry the operation.
• A communication test cannot be executed on the own station, relay
sending station, and stations mounted on the same base unit (main base
unit and extension base unit).
After completion of the cable test, retry the operation.
The transfer destination of the IP data does not support the IP packet
transfer function.
Retry the operation after a while.
Check "Communication Target" in the "IP Communication Test" window.
Check "Communication Target" in the "IP Communication Test" window.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.