Error code
DAF3
Flash ROM failure
H
DAF5
Network module failure
H
DAF6
and
H
Network module failure
DAF7
H
DAF8
and
H
Flash ROM failure
DAF9
H
E000
H
Error detected in CC-Link IE Controller Network
to
(
Manual for the CC-Link IE Controller Network module used)
EFFF
H
F000
H
Error detected in a MELSECNET/H or MELSECNET/10 network system
to
(
MELSECNET/H or MELSECNET/10 Network System Reference Manual)
FEFF
H
460
Error
• The flash ROM may be faulty. Check the wire and cable distances and
grounding condition of each device, and take measures against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures
against noise.
• Execute hardware and self-loopback tests. If a failure occurs again, the
hardware of the master/local module may be faulty. Please consult your
local Mitsubishi representative.
The flash ROM may be faulty. Execute hardware and self-loopback tests. If a
failure occurs again, the hardware of the master/local module may be faulty.
Please consult your local Mitsubishi representative.
Action