System Information Setting Program Example; Specified Device Monitor; System Information - Specified Device Monitor Function; Differences Between Specified Device Monitor Screen And Monitor/Test Screen - Mitsubishi Electric FX3G-5DM Quick Start Manual

Programmable logic controller
Hide thumbs Also See for FX3G-5DM:
Table of Contents

Advertisement

FX3G-5DM QUICK START MANUAL
System signal 1
System
Status
Description
Information
Device type to
Doo
be displayed
D8300 =
Device No. to
Doo+1
Koo
be displayed
Occupies
Doo+2
Screen saver setting time (Forced display)
5 points
Doo+3
Device for display screen protect function
Doo+4
Not used
System signal 2
System
Status
Information
M
+1
M
+2
M
+3
M
+4
M
D8300 =
+5
M
Koo
+6
Occupies
M
5 points
+7
M
+8
M
+9
M
+10 to 14
M

13.2 SYSTEM INFORMATION SETTING PROGRAM EXAMPLE

The following is a program example in which the system information
has been assigned to D50 to D54 and M50 to M64.
M8002
MOV
K50
Initial pulse
MOV
K50

14. SPECIFIED DEVICE MONITOR

The specified device monitor function can change the top screen to the
monitor/test screen for a device specified by the user.
For the specified device monitor function, specify the device type to be
displayed in "Doo" of the system information (system signal 1), and
specify the device number to be displayed in "Doo+1" of the system
information (system signal 1).
It is necessary to turn ON M
specified device monitor screen.
14.1 SYSTEM INFORMATION - SPECIFIED DEVICE
MONITOR FUNCTION
SYSTEM SIGNAL 1
System Information
Description
Device type to be displayed
D oo
D oo+1
Device No. to be displayed *1
*1 Maximum or minimum value of the corresponding device if the device number is set
outside the allowable range.
12
Mitsubishi Electric Automation, Inc.
For specified device monitor function
Description
Request Edit of displayed device data
Edition completion response
Screen saver function invalid
Not used
[ESC] button ON/OFF
Operation
[-] button ON/OFF
button
ON/OFF
[+] button ON/OFF
information
[OK] button ON/OFF
Device for specifying the "Monitor/Test" menu's
current value and setting the value display format
(hexadecimal or decimal).
Specified device monitor display status
Not used
D8300
System information (system No.1) is set at D50 to D54.
D8301
System information (system No.2) is set at M50 to M64.
END
to enable the test operation on the
The table below shows the device type to be displayed in accordance
with the numeric value written in Doo. If any numeric value outside
the range from 1 to 10 is written in Doo, the specified device monitor
function is disabled.
Value stored in Doo
Device Type
1
Input (X)
2
Output( X)
3
Auxiliary relay(M)
4
State (S)
5
Timer (T)
6
Counter (C)
7
Data register (D)
8
Data register (DD)
9
Extended register(R)
10
Extended register(DR)
Others
Not used
SYSTEM SIGNAL 2
Value Stored in Doo
Device Type
Request Edit of displayed device data
ON : Enables the test function.
M
OFF : Disables the test function (and enables only
monitoring).
+1
M
Edit completion response *1
+4
"ESC" key status
M
+5
M
"-" key status
+6
M
"+" key status
+7
"OK" key status
M
Specified device monitor display status
ON: The specified device monitor screen is displayed.
+9
M
OFF: Any screen other than the specified device
monitor screen is displayed.
*1 Turns ON after completion of a test operation for a specified device monitor (or
when the OK or ESC key operated). To turn OFF, the request edit of a specified device
monitor is turned off or it is turned off in the user's program.
14.2 DIFFERENCES BETWEEN SPECIFIED DEVICE MONITOR
SCREEN AND MONITOR/TEST SCREEN
The figure below shows differences between the specified device
monitor screen and the monitor/test screen.
-Specified Device Monitor Screen
-Monitor/Test Screen
When D1000 is specified
When D1000 is monitored
D
1 0
D 1 0 0
0
3 2 7 6
7
D
1
0 0
D
1
0 0
( S p e c i f i e d )
D
1
0 0
In the case of a specified device monitor
screen "specified" is displayed.

14.3 PROGRAM EXAMPLE1 (when monitoring/testing a timer)

In this program example, the device type to be displayed on the
specified device monitor screen is set to "timer (T)" . Sets the device No.
to "T10" .
For testing the timer T10, turn ON M0 to enable the test operation. In
this program example, system information is assigned from D50 to D54
and from M50 to M64.
M8002
MOV
K50
D8300
System information (system No.1) is set at D50 to D54.
Initial pulse
MOV
K50
D8301
System information (system No.2) is set at M50 to M64.
MOV
K5
D50
Sets the device type to "Timer".
MOV
K10
D51
Sets the device No. to "T10".
Test operation
enable command
M0
M50
When M0 turns ON, the test operation for T10 is enabled.
END
0