Parameter Settings For A Master Station; Setting Method - Mitsubishi Electric L26CPU-BT User Manual

Melsec-l cc-link system master/local module
Hide thumbs Also See for L26CPU-BT:
Table of Contents

Advertisement

7.3

Parameter Settings for a Master Station

This chapter describes the parameter settings when the L series master/local module is used as a master station.
7.3.1

Setting method

1.
Open the "Network Parameter" window on a programming tool.
Project window
2.
Check the checkbox next to "Set the station information in the CC-Link configuration window" at
the top of the window.
3.
Input settings in the "Network Parameter" window. (Refer to
4.
Click the [End] button.
5.
Write the settings to the CPU module using the programming tool.
[Online]
6.
The settings are reflected by resetting the CPU module or powering off and on the system. When
the reflection is completed, data link is automatically started in the L series master/local modules.
● To change the settings for a master station or a device station, stop data link in the master station. (Refer to
186, Section 8.3.8)
● When the settings for a device station have been changed, change the settings for the master station accordingly.
76
[Parameter]
[Network Parameter]
[Write to PLC]
[CC-Link]
Page 77, Section 7.3.2)
Page