2 Parameter Description
2.2.9 0-7* Clock Settings
Set the time and date of the internal clock. The internal clock can be used for e.g. Timed Actions, energy log, Trend Analysis, date/time stamps on alarms,
Logged data and Preventive Maintenance.
It is possible to program the clock for Daylight Saving Time / summertime, weekly working days/non-working days including 20 exceptions (holidays
2
etc.). Although the clock settings can be set via the LCP, they can also be set along with timed actions and preventative maintenance functions using the
MCT10 software tool.
NB!
The frequency converter has no back up of the clock function and the set date/time will reset to default (2000-01-01 00:00) after a
power down unless a Real Time Clock module with back up is installed. If no module with back up is installed, it is recommended the
clock function is only used if the frequency converter is integrated into an external system using serial communications, with the system
maintaining synchronization of control equipment clock times. In par. 0-79,
clock has not been set properly, e.g. after a power down.
0-70 Set Date and Time
Range:
2000-01-01
[2000-01-01 00:00]
00:00
2099-12-01
23:59 *
0-71 Date Format
Option:
[0] *
YYYY-MM-DD
[1]
DD-MM-YYYY
[2]
MM/DD/YYYY
0-72 Time Format
Option:
[0] *
24 h
[1]
12 h
0-73 Time Zone Offset
Option:
[0.00]
-12.00 - 13.00
0-74 DST/Summertime
Option:
[0] *
Off
[2]
Manual
38
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Sets the date and time of the internal clock. The format to be used is set in par. 0-71 and 0-72.
NB!
This parameter does not display the actual time. This can be read in par. 0-89.
The clock will not begin counting until a setting different from default has been
made.
Function:
Sets the date format to be used in the LCP.
Sets the date format to be used in the LCP.
Sets the date format to be used in the LCP.
Function:
Sets the time format to be used in the LCP.
Function:
Sets the time zone offset to UTC, this is needed for automatic DST adjustment.
Function:
Choose how Daylight Saving Time/Summertime should be handled. For manual DST/Summertime
enter the start date and end date in par. 0-76
time End
.
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Clock Fault
, it is possible to program for a Warning in case
DST/Summertime Start