2 Parameter Description
6-01 Live Zero Timeout Function
Option:
2
[0] *
Off
[1]
Freeze output
[2]
Stop
[3]
Jogging
[4]
Max. speed
[5]
Stop and trip
100
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Select the time-out function. The function set in par. 6-01
vated if the input signal on terminal 53 or 54 is below 50% of the value in par. 6-10
Low Voltage
, par. 6-12
Terminal 53 Low Current
Terminal 54 Low Current
par. 6-22
for a time period defined in par. 6-00
If several time-outs occur simultaneously, the frequency converter prioritises the time-out functions
as follows:
1.
par. 6-01
Live Zero Timeout Function
Control Timeout Function
2.
par. 8-04
The output frequency of the frequency converter can be:
[1] frozen at the present value
[2] overruled to stop
[3] overruled to jog speed
[4] overruled to max. speed
[5] overruled to stop with subsequent trip
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Programming Guide
Live Zero Timeout Function
will be acti-
Terminal 53
, par. 6-20
Terminal 54 Low Voltage
Live Zero Timeout Time
or
.