VLT Automation VT Drive FC322
Programming Guide
16-10 Power [kW]
Range:
0.00 kW*
[0.00 - 10000.00 kW]
16-11 Power [hp]
Range:
0.00 hp*
[0.00 - 10000.00 hp]
16-12 Motor Voltage
Range:
0.0 V*
[0.0 - 6000.0 V]
16-13 Frequency
Range:
0.0 Hz*
[0.0 - 6500.0 Hz]
16-14 Motor Current
Range:
0.00 A*
[0.00 - 10000.00 A]
16-15 Frequency [%]
Range:
0.00 %*
[-100.00 - 100.00 %]
16-16 Torque [Nm]
Range:
0.0 Nm*
[-30000.0 - 30000.0 Nm]
16-17 Speed [RPM]
Range:
0 RPM*
[-30000 - 30000 RPM]
16-18 Motor Thermal
Range:
0 %*
[0 - 100 %]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
View the motor power in kW. The value shown is calculated on the basis of the actual motor voltage
and motor current. The value is filtered, and therefore approx. 30 ms may pass from when an input
value changes to when the data read-out values change.
Function:
View the motor power in HP. The value shown is calculated on the basis of the actual motor voltage
and motor current. The value is filtered, and therefore approximately 30 ms may pass from when
an input value changes to when the data read-out values change.
Function:
View the motor voltage, a calculated value used for controlling the motor.
Function:
View the motor frequency, without resonance dampening.
Function:
View the motor current measured as a mean value, IRMS. The value is filtered, and thus approxi-
mately 30 ms may pass from when an input value changes to when the data read-out values change.
Function:
View a two-byte word reporting the actual motor frequency (without resonance dampening) as a
percentage (scale 0000-4000 Hex) of par. 4-19
Configuration
index 1 to send it with the Status Word instead of the MAV.
Function:
View the torque value with sign, applied to the motor shaft. Linearity is not exact between 110%
motor current and torque in relation to the rated torque. Some motors supply more than 160%
torque. Consequently, the min. value and the max. value will depend on the max. motor current as
well as the motor used. The value is filtered, and thus approx. 1.3 seconds may pass from when an
input changes value to when the data read-out values change.
Function:
View the actual motor RPM.
Function:
View the calculated thermal load on the motor. The cut-out limit is 100%. The basis for calculation
is the ETRElectronic Thermal Overload function selected in par. 1-90
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
Max Output Frequency
. Set par. 9-16
PCD Read
Motor Thermal Protection
2
.
175