2 Parameter Description
14-20 Reset Mode
Option:
[0]
Manual reset
[1]
Automatic reset x 1
2
[2]
Automatic reset x 2
[3]
Automatic reset x 3
[4]
Automatic reset x 4
[5]
Automatic reset x 5
[6]
Automatic reset x 6
[7]
Automatic reset x 7
[8]
Automatic reset x 8
[9]
Automatic reset x 9
[10] *
Automatic reset x 10
[11]
Automatic reset x 15
[12]
Automatic reset x 20
[13]
Infinite Automatic Reset
14-21 Automatic Restart Time
Range:
10 s*
[0 - 600 s]
160
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Select the reset function after tripping. Once reset, the frequency converter can be restarted.
Select
Manual reset
[0], to perform a reset via [RESET] or via the digital inputs.
Automatic reset x 1...x20
Select
[1]-[12] to perform between one and twenty automatic resets after
tripping.
Infinite Automatic Reset
Select
[13] for continuous resetting after tripping.
NB!
The motor may start without warning. If the specified number of AUTOMATIC
RESETs is reached within 10 minutes, the frequency converter enters Manual
reset [0] mode. After the Manual reset is performed, the setting of par. 14-20
reverts to the original selection. If the number of automatic resets is not reached
within 10 minutes, or when a Manual reset is performed, the internal AUTOMATIC
RESET counter returns to zero.
Function:
Enter the time interval from trip to start of the automatic reset function. This parameter is active
Reset Mode
Automatic reset
when par. 14-20
is set to
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Programming Guide
[1] - [13].