2 Parameter Description
6-62 Terminal X30/8 Max. Scale
Range:
100.00 %*
[0.00 - 200.00 %]
2
6-63 Terminal X30/8 Output Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
6-64 Terminal X30/8 Output Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
110
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Scales the maximum output of the selected analog signal on terminal X30/8. Scale the value to the
desired maximum value of the current signal output. Scale the output to give a lower current than
20 mA at full scale or 20 mA at an output below 100% of the maximum signal value. If 20 mA is
the desired output current at a value between 0 - 100% of the ful-scale output, program the per-
centage value in the parameter, i.e. 50% = 20 mA. If a current between 4 and 20 mA is desired at
maximum output (100%), calculate the percentage value as follows:
20
mA
/
desired maximum current
× 100 %
20
mA
i
.
e
. 10
mA
:
× 100 % = 200 %
mA
10
Function:
Contains the value to apply to the output terminal, when it is configured as [Bus Controlled].
Function:
Contains the value to apply to the output terminal, when it is configured as [Bus Controlled Timeout]
and time-out is detected.
MG.20.W1.22 - VLT is a registered Danfoss trademark