VLT Automation VT Drive FC322
Programming Guide
1-39 Motor Poles
Range:
Application
[2 - 100 ]
dependent*
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Enter the number of motor poles.
Poles
~n
@ 50 Hz
n
2
2700 - 2880
4
1350 - 1450
6
700 - 960
The table shows the number of poles for normal speed ranges of various motor types. Define motors
designed for other frequencies separately. The motor pole value is always an even number, because
it refers to the total number of poles, not pairs of poles. The frequency converter creates the initial
setting of par. 1-39
Motor Poles
based on par. 1-23
par. 1-25
Motor Nominal Speed Motor Nominal Speed
This parameter cannot be adjusted while the motor is running.
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
~n
@60 Hz
n
3250 - 3460
1625 - 1730
840 - 1153
Motor Frequency Motor Frequency
.
2
and
45