VLT Automation VT Drive FC322
Programming Guide
9-53 Profibus Warning Word
Range:
0*
[0 - 65535 ]
Read only
Bit:
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
9-63 Actual Baud Rate
Option:
[0]
9,6 kbit/s
[1]
19,2 kbit/s
[2]
93,75 kbit/s
[3]
187,5 kbit/s
[4]
500 kbit/s
[6]
1500 kbit/s
[7]
3000 kbit/s
[8]
6000 kbit/s
[9]
12000 kbit/s
[10]
31,25 kbit/s
[11]
45,45 kbit/s
[255] *
No baudrate found
9-65 Profile Number
Range:
0*
[0 - 0 ]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
This parameter displays Profibus communication warnings. Please refer to the
Instructions
for further information.
Meaning:
Connection with DP-master is not ok
Not used
FDLNDL (Fieldbus Data link Layer) is not ok
Clear data command received
Actual value is not updated
Baudrate search
PROFIBUS ASIC is not transmitting
Initializing of PROFIBUS is not ok
Frequency converter is tripped
Internal CAN error
Wrong configuration data from PLC
Wrong ID sent by PLC
Internal error occured
Not configured
Timeout active
Warning 34 active
Function:
This parameter displays the actual Profibus baud rate. The Profibus Master automatically sets the
baud rate.
Function:
This parameter contains the profile identification. Byte 1 contains the profile number and byte 2 the
version number of the profile.
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
Profibus Operating