2 Parameter Description
[137]
Speed 4-20mA
[138]
Torque 4-20mA
[139]
Bus ctrl.
[140]
Bus ctrl. 4-20 mA
2
[141]
Bus ctrl t.o.
[142]
Bus ctrl t.o. 4-20mA
[143]
Ext. CL 1 4-20mA
[144]
Ext. CL 2 4-20mA
[145]
Ext. CL 3 4-20mA
[146]
Cascade Ref. 4-20mA
[150]
Out frq 0-Fmax 4-20mA
NB!
Values for setting the Minimum Reference is found in open loop par. 3-02
Feedb.
- values for maximum reference for open loop is found in par. 3-03
Feedb.
.
6-51 Terminal 42 Output Min Scale
Range:
0.00 %*
[0.00 - 200.00 %]
6-52 Terminal 42 Output Max Scale
Range:
100.00 %*
[0.00 - 200.00 %]
106
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
: 0 - Speed High Limit (par. 4-13 and par. 4-14)
:
: 0 - 100%, (0-20 mA)
: 0 - 100%
: 0 - 100%, (0-20 mA)
: 0 - 100%
: 0 - 100%
: 0 - 100%
: 0 - 100%
:
:
Minimum Reference
Maximum Reference
Function:
Scale for the minimum output (0 or 4 mA) of the analogue signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. 6-50
42 Output
.
Function:
Scale for the maximum output (20 mA) of the analog signal at terminal 42.
Set the value to be the percentage of the full range of the variable selected in par. 6-50
42 Output
.
It is possible to get a value lower than 20 mA at full scale by programming values >100% by using
a formula as follows:
20
mA
/
desired maximum current
× 100 %
mA
20
i
.
e
. 10
mA
:
× 100 % = 200 %
10
mA
MG.20.W1.22 - VLT is a registered Danfoss trademark