2 Parameter Description
25-45 Staging Speed [Hz]
Range:
0.0 Hz*
[0.0 - 0.0 Hz]
2
25-46 Destaging Speed [RPM]
Range:
0 RPM*
[0 - 0 RPM]
25-47 Destaging Speed [Hz]
Range:
0.0 Hz*
[0.0 - 0.0 Hz]
248
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Readout of the below calculated value for Staging Speed When adding a fixed speed pump, in order
to prevent an overshoot of pressure, the variable speed pump ramps down to a lower speed. When
the variable speed pump reaches the "Staging Speed" the fixed speed pump is staged on. Staging
Speed calculation is based on par. 25-42
[Hz]
.
Staging Speed is calculated with the following formula:
STAGE
%
=
where n
HIGH
100
STAGE
HIGH
Staging Threshold.
Function:
Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump,
in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed.
When the variable speed pump reaches the "Destaging Speed" the fixed speed pump is destaged.
Destaging Speed is calculated based on par. 25-43
High Limit [RPM]
.
Destaging Speed is calculated with the following formula:
DESTAGE
%
=
where n
100
DESTAGE
HIGH
value of Destaging Threshold.
Function:
Readout of the below calculated value for Destaging Speed. When removing a fixed speed pump,
in order to prevent an undershoot of pressure, the variable speed pump ramps up to a higher speed.
When the variable speed pump reaches the "Destaging Speed" the fixed speed pump is destaged.
Destaging Speed is calculated based on par. 25-43
High Limit [Hz]
.
Destaging Speed is calculated with the following formula:
DESTAGE
%
=
100
DESTAGE
HIGH
where n
is Motor Speed High Limit and n
HIGH
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Staging Threshold
Motor Speed High Limit
, and par. 4-14
is Motor Speed High Limit and n
STAGE100%
Destaging Threshold
, and par. 4-13
is Motor Speed High Limit and n
HIGH
DESTAGE100%
Destaging Threshold
, and par. 4-14
is the value of Destaging Threshold.
DESTAGE100%
Programming Guide
is the value of
Motor Speed
is the
Motor Speed