2 Parameter Description
22-23 No-Flow Function
Option:
2
[0] *
Off
[1]
Sleep Mode
[2]
Warning
[3]
Alarm
22-24 No-Flow Delay
Range:
10 s*
[1 - 600 s]
22-26 Dry Pump Function
Option:
[0] *
Off
[1]
Warning
[2]
Alarm
[3]
Manual Reset Alarm
22-27 Dry Pump Delay
Range:
10 s*
[0 - 600 s]
22-28 No-Flow Low Speed [RPM]
Range:
0*
[Motor Min. Speed - Motor Max.
Speed]
22-29 No-Flow Low Speed [Hz]
Range:
0*
[Motor Min. Speed - Motor Max.
Speed]
2.19.3 22-3* No-Flow Power Tuning
Tuning Sequence, if not choosing
1.
Close the main valve to stop flow
2.
Run with motor until the system has reached normal operating temperature
214
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Common actions for Low Power Detection and Low Speed Detection (Individual selections not pos-
sible).
Messages in the Local Control Panel display (if mounted) and/or signal via a relay or a digital output.
The frequency converter trips and motor stays stopped until reset.
Function:
Set the time Low Power/Low Speed must stay detected to activate signal for actions. If detection
disappears before run out of the timer, the timer will be reset.
Function:
Low Power Detection
either par. 22-3*,
No Flow Power Tuning
Pump Detection.
Messages in the Local Control Panel display (if mounted) and/or signal via a relay or a digital output.
The frequency converter trips and motor stays stopped until reset.
Function:
Defines for how long the Dry Pump condition must be active before activating Warning or Alarm
Function:
Used to set the speed for no-flow low speed detection.
If a low speed detection at a speed different from the motor minimum speed is needed, this pa-
rameter may be used.
Function:
Used to set the speed for no-flow low speed detection.
If a low speed detection at a speed different from the motor minimum speed is needed, this pa-
rameter may be used.
Auto Set Up
in par. 22-20
Low Power Auto Set-up
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Low Power Detection
must be Enabled (par. 22-21
, or par. 22-20
Low Power Auto Set-up
:
Programming Guide
) and commissioned (using
) in order to use Dry