VLT Automation VT Drive FC322
Programming Guide
8-55 Set-up Select
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. 8-01
8-56 Preset Reference Select
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. 8-01
2.9.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communication via the FC Port.
8-80 Bus Message Count
Range:
0*
[0 - 0 ]
8-81 Bus Error Count
Range:
0*
[0 - 0 ]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Select control of the frequency converter set-up selection via the terminals (digital input) and/or via
the fieldbus.
Activates the set-up selection via a digital input.
Activates the set-up selection via the serial communication port or fieldbus option.
Activates the set-up selection via the fieldbus/serial communication port, AND additionally via one
of the digital inputs.
Activate the set-up selection via the fieldbus/serial communication port OR via one of the digital
inputs.
Control Site
is set to [0]
Digital and control word
Function:
Select control of the frequency converter Preset Reference selection via the terminals (digital input)
and/or via the fieldbus.
Activates Preset Reference selection via a digital input.
Activates Preset Reference selection via the serial communication port or fieldbus option.
Activates Preset Reference selection via the fieldbus/serial communication port, AND additionally
via one of the digital inputs.
Activates the Preset Reference selection via the fieldbus/serial communication port OR via one of
the digital inputs.
Control Site
Digital and control word
is set to [0]
Function:
This parameter shows the number of valid telegrams detected on the bus.
Function:
This parameter shows the number of telegrams with faults (e.g. CRC fault), detected on the bus.
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
.
.