VLT Automation VT Drive FC322
Programming Guide
[1] *
Enabled
26-20 Terminal X42/3 Low Voltage
Range:
0.07 V*
[Application dependant]
26-21 Terminal X42/3 High Voltage
Range:
10.00 V*
[Application dependant]
26-24 Term. X42/3 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
26-25 Term. X42/3 High Ref./Feedb. Value
Range:
100.000*
[-999999.999 - 999999.999 ]
26-26 Term. X42/3 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
26-27 Term. X42/3 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
26-30 Terminal X42/5 Low Voltage
Range:
0.07 V*
[Application dependant]
26-31 Terminal X42/5 High Voltage
Range:
10.00 V*
[Application dependant]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
Term. X42/3 Low Ref./Feedb. Value
feedback value set in par. 26-24
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 26-25
Function:
Enter the analog input scaling value that corresponds to the low voltage value set in
par. 26-20
Terminal X42/3 Low Voltage
Function:
Enter the analog input scaling value that corresponds to the high voltage value set in
par. 26-21
Terminal X42/3 High Voltage
Function:
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
noise in terminal X42/3. A high time constant value improves dampening but also increases the time
delay through the filter. This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to enable the Live Zero monitoring. E.g. where the analog input
is a part of the frequency converter control, rather than being used as part of a decentral I/O system,
such as a Building Management System.
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
feedback value set in par. 26-34
Term. X42/5 Low Ref./Feedb. Value
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
ence/feedback value set in par. 26-35
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
.
Term. X42/3 High Ref./Feedb. Value
.
.
.
.
Term. X42/5 High Ref./Feedb. Value
.
2
257