VLT Automation VT Drive FC322
Programming Guide
2.21.2 25-0* System Settings
Parameters related to control principles and configuration of the system.
25-00 Cascade Controller
Option:
[0] *
Disabled
[1]
Basic Cascade Ctrl
[2] *
Motor Alternation Only
25-02 Motor Start
Option:
[0] *
Direct on Line
[1]
Soft Starter
[2]
Star Delta
25-04 Pump Cycling
Option:
[0] *
Disabled
[1]
Enabled
25-05 Fixed Lead Pump
Option:
[0]
No
[1] *
Yes
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
For operation of multiple devices (pump/fan) systems where capacity is adapted to actual load by
means of speed control combined with on/off control of the devices. For simplicity only pump sys-
tems are described.
The Cascade Controller is not active. All built-in relays assigned to pump motors in the cascade
function will be de-energized. If a variable speed pump is connected to the frequency converter
directly (not controlled by a built-in relay); this pump/fan will be controlled as a single pump system.
The Cascade Controller is active and will stage/destage pumps according to load on the system.
Function:
Motors are connected to the mains directly with a contactor or with a soft starter. When the value
of par. 25-02
Motor Start
is set to an option other than
Pump Alternation
is automatically set to the default of
Each fixed speed pump is connected to line directly via a contactor.
Each fixed speed pump is connected to line via a soft starter.
Function:
To provide equal hours of operation with fixed speed pumps, the pump use can be cycled. The
selection of pump cycling is either "first in – last out" or equal running hours for each pump.
The fixed speed pumps will be connected in the order 1 – 2 and disconnected in the order 2 – 1.
(First in – last out).
The fixed speed pumps will be connected/disconnected to have equal running hours for each pump.
Function:
Fixed Lead Pump means that the variable speed pump is connected directly to the frequency con-
verter and if a contactor is applied between frequency converter and pump, this contactor will not
be controlled by the frequency converter.
Lead Pump Alternation
If operating with par. 25-50
be set to
No
[0].
The lead pump function can alternate between the pumps controlled by the two built in relays. One
pump must be connected to the built-in RELAY 1, and the other pump to RELAY 2. The pump
function (Cascade Pump1 and Cascade Pump2) will automatically be assigned to the relays (maxi-
mum two pumps can in this case be controlled from the frequency converter).
The lead pump will be fixed (no alternation) and connected directly to the frequency converter. The
Lead Pump Alternation
par. 25-50
is automatically set to
2 can be assigned to separate fixed speed pumps. In total three pumps can be controlled by the
frequency converter.
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
Direct on Line
[0], then par. 25-50
Direct on Line
[0].
Off
set to other than
[0], this parameter must
Off
[0]. Built-in relays Relay 1 and Relay
2
Lead
241