2 Parameter Description
16-22 Torque [%]
Range:
0 %*
[-200 - 200 %]
2
2.15.4 16-3* Drive Status
Parameters for reporting the status of the frequency converter.
16-30 DC Link Voltage
Range:
0 V*
[0 - 10000 V]
16-32 Brake Energy /s
Range:
0.000 kW*
[0.000 - 10000.000 kW]
16-33 Brake Energy /2 min
Range:
0.000 kW*
[0.000 - 10000.000 kW]
16-34 Heatsink Temp.
Range:
0 C*
[0 - 255 C]
16-35 Inverter Thermal
Range:
0 %*
[0 - 100 %]
16-36 Inv. Nom. Current
Range:
Application
[0.01 - 10000.00 A]
dependent*
16-37 Inv. Max. Current
Range:
Application
[0.01 - 10000.00 A]
dependent*
16-38 SL Controller State
Range:
0*
[0 - 100 ]
176
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
This is a read out parameter only.
Shows the actual torque yielded in percentage of the rated torque, based on the setting of the motor
size and rated speed in par. 1-20
Motor Power [kW]
Motor Nominal Speed
par. 1-25
.
This is the value monitored by the
Broken Belt Function
Function:
View a measured value. The value is filtered with an 30 ms time constant.
Function:
View the brake power transmitted to an external brake resistor, stated as an instantaneous value.
Function:
View the brake power transmitted to an external brake resistor. The mean power is calculated on
an average basis for the most recent 120 seconds.
Function:
View the frequency converter heatsink temperature. The cut-out limit is 90 ± 5 C, and the motor
cuts back in at 60 ± 5 C.
Function:
View the percentage load on the inverter.
Function:
View the inverter nominal current, which should match the nameplate data on the connected motor.
The data are used for calculation of torque, motor protection, etc.
Function:
View the inverter maximum current, which should match the nameplate data on the connected
motor. The data are used for calculation of torque, motor protection, etc.
Function:
View the state of the event under execution by the SL controller.