1.7 Warnings and Alarms 1.8.1 Mains Supply 3x380-480 V AC 1.8.2 EMC Test Results 1.9 Special Conditions 1.9.1 Derating for Ambient Temperature and Switching Frequency 1.9.2 Derating for Low Air Pressure ® MG18F402 - VLT is a registered Danfoss trademark...
Installation at high altitudes the Discharge Time table. Failure to wait the specified time For altitudes above 2 km, contact Danfoss regarding PELV. after power has been removed before doing service or repair could result in death or serious injury.
Illustration 1.1 IP20 0.37-22 kW 380-480 V EMC screw Table 1.2 Legend to Illustration 1.1 On all units, set 14-50 RFI filter to Off when operating in IT mains. CAUTION If reinserted, only use M3x12 screw. ® MG18F402 - VLT is a registered Danfoss trademark...
IP20 55-75 kW/ 200/7.9 100-120 hp IP20 90 kW/ 225/8.9 125 hp Table 1.4 NOTE With IP21/Nema Type1 option kit mounted, a distance of 50 mm between the units is required. ® MG18F402 - VLT is a registered Danfoss trademark...
Table 1.7: Enclosure Clearance needed for free air passage [mm] Frame IP class Above unit Below unit Table 1.7 Clearance Needed for Free Air Passage ® MG18F402 - VLT is a registered Danfoss trademark...
Also see EMC-Correct Installation in the Design Guide. Mount the earth wires to earth terminal. Connect motor to terminals U, V and W. Mount mains supply to terminals L1, L2 and L3 and tighten. ® MG18F402 - VLT is a registered Danfoss trademark...
Page 9
Illustration 1.2 IP20 380-480 V, 0.37-22 kW Line Earth Motor Relays Table 1.9 Legend to Illustration 1.2 Illustration 1.4 IP20 380-480 V, 55-75 kW Line Relays Earth Motor Table 1.11 Legend to Illustration 1.4 ® MG18F402 - VLT is a registered Danfoss trademark...
General points to be observed to ensure EMC-correct electrical installation. Short circuit protection Danfoss recommends using the fuses mentioned in the • following tables to protect service personnel or other Use only screened/armoured motor cables and equipment in case of an internal failure in the unit or screened/armoured control cables.
Page 11
Mains-supply and between mains motor cable Reinforced protective earth Illustration 1.6 EMC-correct Electrical Installation, FCM 106 NOTE For North America use metal conduits instead of shielded cables. ® MG18F402 - VLT is a registered Danfoss trademark...
27 29 42 45 50 53 54 0/4-20mA A OUT / DIG OUT 0/4-20mA A OUT / DIG OUT 12 20 55 COM A IN COM DIG IN Illustration 1.9 Control Terminals ® MG18F402 - VLT is a registered Danfoss trademark...
61 on 116,117 and 118 unites 24V (NPN) OV (PNP) (PNP)-Source (NPN)-Sink Illustration 1.10 Electrical Overview NOTE There is no access to UDC- and UDC+ on the following units: IP20 380-480 V, 30-90 kW ® MG18F402 - VLT is a registered Danfoss trademark...
Motor direction is shown to the bottom left of the display Software. This software can either be ordered using code – indicated by a small arrow pointing either clockwise or number 130B1000 or downloaded from the Danfoss Web counterclockwise. site: www.danfoss.com/BusinessAreas/DrivesSolutions/softwar-...
Press [OK] to start the wizard. If [Back] is pressed, the frequency converter returns to the status screen. Press OK to start Wizard Push Back to skip it Setup 1 Illustration 1.13 ® MG18F402 - VLT is a registered Danfoss trademark...
Page 16
AMA running AMA Failed Wizard completed Press OK ----- Press OK to accept Setup 1 Setup 1 Setup 1 0.0 Hz 0.0 kW Setup 1 AMA failed AMA OK Illustration 1.14 ® MG18F402 - VLT is a registered Danfoss trademark...
Page 17
1-40 Força Contra Eletro- 10-9000 Size related Line-Line RMS back EMF voltage at 1000 RPM. motriz em 1000RPM 1-73 Flying Start When PM is selected, Flying Start is enabled and can not disable. ® MG18F402 - VLT is a registered Danfoss trademark...
Page 18
Current reference value. 6-19 Terminal 53 mode [0] Current Select if terminal 53 is used for current- or voltage [1] Voltage input. Table 1.17 The Start-up Wizard for Open Loop Applications ® MG18F402 - VLT is a registered Danfoss trademark...
Page 19
6-21 T54 high Voltage 0220 13.30 20-93 PI Proportional Gain 00.50 6-25 T54 high Feedback 6-25 T54 high Feedback 0050 0050 20-94 PI integral time 0020.00 1-29 Automatic Motor Adaption Illustration 1.15 ® MG18F402 - VLT is a registered Danfoss trademark...
Page 20
Select if terminal 54 is used for current- or [1] Voltage voltage input. 6-20 Terminal 54 Low Voltage 0-10 V 0.07 V Enter the voltage that corresponds to the low reference value. ® MG18F402 - VLT is a registered Danfoss trademark...
Page 21
1-20 Motor 0.12-110 kW/ Size related Enter motor Power 0.16-150 hp power from nameplate data. 1-22 Motor 50.0-1000.0 V Size related Enter motor Voltage voltage from nameplate data. ® MG18F402 - VLT is a registered Danfoss trademark...
Page 22
Size related Ramp down time Ramp Down from rated Time 1-23 Motor Frequency to 0. 4-12 Motor 0.0-400 Hz 0.0 Hz Enter the Speed Low minimum limit Limit [Hz] for low speed. ® MG18F402 - VLT is a registered Danfoss trademark...
The alternation of the lead pump can take place at a command signal or at staging (adding lag pump). The command can be a manual alternation or an alternation event signal. If the alternation event is selected, ® MG18F402 - VLT is a registered Danfoss trademark...
[Auto On] Starts and stops according to commands via Staging/Destaging terminals or serial bus cascade controller only can work when drive in "Auto ON" mode Table 1.21 Function of Keys on LCP ® MG18F402 - VLT is a registered Danfoss trademark...
When 25-04 Pump Cycling=[1] Enable: maximum 4 When 25-04 Pump Cycling=[1] Enable: maximum 3 pumps. pumps. 2 relays and 2 digital outputs are available. 2 relays, 2 digital outputs and 2 analog outputs are available. ® MG18F402 - VLT is a registered Danfoss trademark...
Phase Function. Motor phase W is missing. Check the phase. See 4-58 Missing W phase loss Motor Phase Function. Internal fault Contact your local Danfoss supplier. Overload on Terminal 27, Digital Output Overload on Terminal 27, Digital Output. Overload on...
Page 30
Exceeded Fire Mode has suppressed one or more warranty voiding alarms. The power or switch mode power supply has been exchanged. (Only on 400 V 30-90 kW units). Contact your local Danfoss New sparepart supplier. The frequency converter has a new type code (only on 400 V, New Typecode 30-90 kW units).
The unit is suitable for use on a circuit capable of delivering not more than 100.000 RMS symmetrical Amperes, 240/480 V maximum. Motor output (U, V, W) Output voltage 0-100% of supply voltage plus Output frequency 0-200 Hz (VVC ), 0-400 Hz (u/f) Switching on output Unlimited Ramp times 0.05-3600 s ® MG18F402 - VLT is a registered Danfoss trademark...
Page 34
Max. voltage at analog output 17 V Accuracy on analog output Max. error: 0.4% of full scale Resolution on analog output 10 bit Terminal 42 and 45 can also be programmed as digital outputs. ® MG18F402 - VLT is a registered Danfoss trademark...
Page 35
Minimum ambient temperature at reduced performance, enclosure frame H6-H10 -30 to +65/70 °C Temperature during storage/transport Maximum altitude above sea level without derating 1000 m Maximum altitude above sea level with derating 3000 m ® MG18F402 - VLT is a registered Danfoss trademark...
1.9.2 Derating for Low Air Pressure The cooling capability of air is decreased at low air pressure. For altitudes above 2000 m, contact Danfoss regarding PELV. Below 1000 m altitude no de-rating is necessary, but above 1000 m the ambient temperature or the maximum output current should be decreased.