Danfoss VLT Automation VT Drive FC 322 Programming Manual page 104

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

2 Parameter Description
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
2
6-17 Terminal 53 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
2.8.4 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
0.07 V*
[Application dependant]
6-21 Terminal 54 High Voltage
Range:
10.00 V*
[Application dependant]
6-22 Terminal 54 Low Current
Range:
4.00 mA*
[Application dependant]
6-23 Terminal 54 High Current
Range:
20.00 mA*
[Application dependant]
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
102
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
electrical noise in terminal 53. A high time constant value improves dampening but also increases
the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system (e.g. when not part of any frequency converter
related control functions, but feeding an external control system with data)
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
Terminal 54 Low Ref./Feedb. Value
feedback value, set in par. 6-24
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
Terminal 54 High Ref./Feedb. Value
ence/feedback value set in par. 6-25
Function:
Enter the low current value. This reference signal should correspond to the low reference/feedback
Terminal 54 Low Ref./Feedb. Value
value, set in par. 6-24
to activate the Live Zero Time-out Function in par. 6-01
Function:
Enter the high current value corresponding to the high reference/feedback value set in
Terminal 54 High Ref./Feedb. Value
par. 6-25
Function:
Enter the analog input scaling value that corresponds to the low voltage/low current value set in
Terminal 54 Low Voltage
par. 6-20
and par. 6-22
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Programming Guide
.
.
. The value must be set at >2 mA in order
Live Zero Timeout Function
.
.
Terminal 54 Low Current
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt dc 322