Danfoss VLT Automation VT Drive FC 322 Programming Manual page 95

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

VLT Automation VT Drive FC322
Programming Guide
2.7.6 5-5* Pulse Input
The pulse input parameters are used to define an appropriate window for the impulse reference area by configuring the scaling and filter settings for the
pulse inputs. Input terminals 29 or 33 act as frequency reference inputs. Set terminal 29 (par. 5-13
Terminal 33 Digital Input
(par. 5-15
5-50 Term. 29 Low Frequency
Range:
100 Hz*
[0 - 110000 Hz]
5-51 Term. 29 High Frequency
Range:
100 Hz*
[0 - 110000 Hz]
5-52 Term. 29 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
5-53 Term. 29 High Ref./Feedb. Value
Range:
100.000*
[-999999.999 - 999999.999 ]
5-54 Pulse Filter Time Constant #29
Range:
100 ms*
[1 - 1000 ms]
5-55 Term. 33 Low Frequency
Range:
100 Hz*
[0 - 110000 Hz]
5-56 Term. 33 High Frequency
Range:
100 Hz*
[0 - 110000 Hz]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Pulse input
) to
[32]. If terminal 29 is used as an input, then set par. 5-02
Function:
Enter the low frequency limit corresponding to the low motor shaft speed (i.e. low reference value)
in par. 5-52
Term. 29 Low Ref./Feedb. Value
Function:
Enter the high frequency limit corresponding to the high motor shaft speed (i.e. high reference
value) in par. 5-53
Term. 29 High Ref./Feedb. Value
Function:
Enter the low reference value limit for the motor shaft speed [RPM]. This is also the lowest feedback
value, see also par. 5-57
Function:
Enter the high reference value [RPM] for the motor shaft speed and the high feedback value, see
also par. 5-58
Term. 33 High Ref./Feedb. Value
Function:
Enter the pulse filter time constant. The pulse filter dampens oscillations of the feedback signal,
which is an advantage if there is a lot of noise in the system. A high time constant value results in
better dampening but also increases the time delay through the filter.
This parameter cannot be adjusted while the motor is running.
Function:
Enter the low frequency corresponding to the low motor shaft speed (i.e. low reference value) in
Term. 33 Low Ref./Feedb. Value
par. 5-57
Function:
Enter the high frequency corresponding to the high motor shaft speed (i.e. high reference value) in
Term. 33 High Ref./Feedb. Value
par. 5-58
MG.20.W1.22 - VLT is a registered Danfoss trademark
Terminal 29 Digital Input
Terminal 29 Mode
. Refer to the diagram in this section.
.
Term. 33 Low Ref./Feedb. Value
.
.
.
.
2 Parameter Description
) or terminal 33
Input
to
[0].
2
93