2 Parameter Description
[60]
Logic rule 4
[61]
Logic rule 5
[70]
SL Time-out 3
[71]
SL Time-out 4
2
[72]
SL Time-out 5
[73]
SL Time-out 6
[74]
SL Time-out 7
[80]
No Flow
[81]
Dry Pump
[82]
End of Curve
[83]
Broken Belt
13-03 Reset SLC
Option:
[0] *
Do not reset SLC
[1]
Reset SLC
2.12.3 13-1* Comparators
Comparators are used for comparing continuous variables (i.e. output frequency, output current, analog input etc.) to fixed preset values. In addition,
there are digital values that will be compared to fixed time values. See explanation in par. 13-10
in each scan interval. Use the result (TRUE or FALSE) directly. All parameters in this parameter group are array parameters with index 0 to 5. Select index
0 to programme Comparator 0, select index 1 to programme Comparator 1, and so on.
13-10 Comparator Operand
Array [4]
Option:
[0] *
DISABLED
[1]
Reference
[2]
Feedback
[3]
Motor speed
[4]
Motor current
[5]
Motor torque
[6]
Motor power
[7]
Motor voltage
[8]
DC-link voltage
[9]
Motor thermal
[10]
Drive thermal
[11]
Heat sink temp.
[12]
Analog input AI53
[13]
Analog input AI54
[14]
Analog input AIFB10
144
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Use the result of logic rule 4 in the logic rule.
Use the result of logic rule 5 in the logic rule.
Use the result of timer 3 in the logic rule.
Use the result of timer 4 in the logic rule.
Use the result of timer 5 in the logic rule.
Use the result of timer 6 in the logic rule.
Use the result of timer 7 in the logic rule.
Function:
Retains programmed settings in all group 13 parameters (13-*).
Resets all group 13 parameters (13-*) to default settings.
Function:
Select the variable to be monitored by the comparator.
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Programming Guide
Comparator Operand
. Comparators are evaluated once