VLT Automation VT Drive FC322
Programming Guide
9-70 Programming Set-up
Option:
[0]
Factory setup
[1]
Set-up 1
[2]
Set-up 2
[3]
Set-up 3
[4]
Set-up 4
[9] *
Active Set-up
This parameter is unique to LCP and fieldbuses. See also par. 0-11
9-71 Profibus Save Data Values
Option:
[0] *
Off
[1]
Store edit setup
[2]
Store all setups
9-72 ProfibusDriveReset
Option:
[0] *
No action
[1]
Power-on reset
[2]
Power-on reset prep
[3]
Comm option reset
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:
0*
[0 - 9999 ]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Select the set-up to be edited.
Uses default data. This option can be used as a data source to return the other set-ups to a known
state.
Edits Set-up 1.
Edits Set-up 2.
Edits Set-up 3.
Edits Set-up 4.
Follows the active set-up selected in par. 0-10
Programming Set-up
.
Function:
Parameter values changed via Profibus are not automatically stored in non-volatile memory. Use
this parameter to activate a function that stores parameter values in the EEPROM non-volatile
memory, so changed parameter values will be retained at power-down.
Deactivates the non-volatile storage function.
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
Stores all parameter values for all set-ups in the non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
Function:
Resets frequency converter upon power-up, as for power-cycle.
Resets the Profibus option only, useful after changing certain settings in parameter group 9-**, e.g.
Node Address
par. 9-18
.
When reset, the frequency converter disappears from the fieldbus, which may cause a communi-
cation error from the master.
Function:
This parameter displays a list of all the defined frequency converter parameters available for Profi-
bus.
MG.20.W1.22 - VLT is a registered Danfoss trademark