Danfoss VLT Automation VT Drive FC 322 Programming Manual page 106

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

2 Parameter Description
6-37 Term. X30/11 Live Zero
Option:
2
[0] *
Disabled
[1]
Enabled
2.8.6 6-4* Analog Input 4 MCB 101
Parameter group for configuring the scale and limits for analog input 4 (X30/12) placed on option module MCB 101.
6-40 Terminal X30/12 Low Voltage
Range:
0.07 V*
[Application dependant]
6-41 Terminal X30/12 High Voltage
Range:
10.00 V*
[Application dependant]
6-44 Term. X30/12 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
6-45 Term. X30/12 High Ref./Feedb. Value
Range:
100.000*
[-999999.999 - 999999.999 ]
6-46 Term. X30/12 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
104
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
This parameter makes it possible to disable the Live Zero monitoring. E.g. to be used if the analog
outputs are used as part of a decentral I/O system (e.g. when not part of any frequency converter
related control functions, but feeding an external control system with data)
Function:
Sets the analog input scaling value to correspond to the low reference/feedback value set in
Term. X30/12 Low Ref./Feedb. Value
par. 6-44
Function:
Sets the analog input scaling value to correspond to the high reference/feedback value set in
Term. X30/12 High Ref./Feedb. Value
par. 6-45
Function:
Sets the analog output scaling value to correspond to the low voltage value set in par. 6-40
X30/12 Low Voltage
.
Function:
Sets the analog input scaling value to correspond to the high voltage value set in par. 6-41
X30/12 High Voltage
.
Function:
st
A 1
order digital low pass filter time constant for suppressing electrical noise on terminal X30/12.
par. 6-46
Term. X30/12 Filter Time Constant
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Programming Guide
.
.
cannot be changed while the motor is running.
Terminal
Terminal