Danfoss VLT Automation VT Drive FC 322 Programming Manual page 117

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

VLT Automation VT Drive FC322
Programming Guide
8-37 Maximum Inter-Char Delay
Range:
Application
[Application dependant]
dependent*
8-40 Telegram Selection
Option:
[1] *
Standard telegram 1
[100]
None
[101]
PPO 1
[102]
PPO 2
[103]
PPO 3
[104]
PPO 4
[105]
PPO 5
[106]
PPO 6
[107]
PPO 7
[108]
PPO 8
[200]
Custom telegram 1
[202]
Custom telegram 3
2.9.5 8-5* Digital/Bus
Parameters for configuring the control word Digital/Bus merging.
8-50 Coasting Select
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3] *
Logic OR
NB!
This parameter is active only when par. 8-01
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Function:
Enables use of freely configurable telegrams or standard telegrams for the FC port.
Function:
Select control of the coasting function via the terminals (digital input) and/or via the bus.
Activates Start command via a digital input.
Activates Start command via the serial communication port or fieldbus option.
Activates Start command via the fieldbus/serial communication port, AND additionally via one of the
digital inputs.
Activates Start command via the fieldbus/serial communication port OR via one of the digital inputs.
Control Site
Digital and control word
is set to [0]
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description
.
2
115

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vlt dc 322

Table of Contents