2 Parameter Description
EXAMPLE 3:
Variable value= REFERENCE, range= Min ref - Max ref
Range needed for output= Min ref (0%) - Max ref (100%), 0-10 mA
Output signal 0 or 4 mA is needed at Min ref - set par. 6-51
Output signal 10 mA is needed at Max ref (100% of range) - set par. 6-52
2
(20 mA / 10 mA x 100%=200%).
6-53 Terminal 42 Output Bus Control
Range:
0.00 %*
[0.00 - 100.00 %]
6-54 Terminal 42 Output Timeout Preset
Range:
0.00 %*
[0.00 - 100.00 %]
2.8.8 6-6* Analog Output 2 MCB 101
Analog outputs are current outputs: 0/4 - 20 mA. Common terminal (terminal X30/8) is the same terminal and electrical potential for analog common
connection. Resolution on analog output is 12 bit.
6-60 Terminal X30/8 Output
Option:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
108
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Terminal 42 Output Min Scale
to 0%
Terminal 42 Output Max Scale
Function:
Holds the level of Output 42 if controlled by bus.
Function:
Holds the preset level of Output 42.
In case of a bus timeout and a timeout function is selected in par. 6-50
output will preset to this level.
Function:
: 0 - 100 Hz, (0-20 mA)
: Minimum reference - Maximum reference, (0-20 mA)
Maximum Reference/Feedb.
: -200% to +200% of par. 20-14
: 0 - Inverter Max. Current (par. 16-37
Inv. Max. Current
: 0 - Torque limit (par. 4-16
Torque Limit Motor Mode
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
Programming Guide
to 200%
Terminal 42 Output
, (0-20 mA)
), (0-20 mA)
), (0-20 mA)