2 Parameter Description
2.21.4 25-4* Staging Settings
Parameters determining conditions for staging/destaging the pumps.
25-40 Ramp Down Delay
Range:
2
10.0 s*
[0.0 - 120.0 s]
25-41 Ramp Up Delay
Range:
2.0 s*
[0.0 - 12.0 s]
25-42 Staging Threshold
Range:
Application
[Application dependant]
dependent*
246
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
When adding a fixed speed pump controlled by a soft starter, it is possible to delay the ramp down
of the lead pump until a preset time after the start of the fixed speed pump to eliminate pressure
surges or water hammer in the system.
Soft Starter
Only to be used if
[1] is selected in par. 25-02
Function:
When removing a fixed speed pump controlled by a soft starter, it is possible to delay the ramp up
of the lead pump until a preset time after the stopping of the fixed speed pump to eliminate pressure
surges or water hammer in the system.
Soft Starter
Only to be used if
[1] is selected in par. 25-02