Danfoss VLT Automation VT Drive FC 322 Programming Manual page 261

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

VLT Automation VT Drive FC322
Programming Guide
26-40 Terminal X42/7 Output
Option:
[0] *
No operation
[100]
Output freq. 0-100
[101]
Reference Min-Max
[102]
Feedback +-200%
[103]
Motor cur. 0-Imax
[104]
Torque 0-Tlim
[105]
Torque 0-Tnom
[106]
Power 0-Pnom
[107]
Speed 0-HighLim
[108]
Torque +-160%
[109]
Out frq 0-Fmax
[113]
Ext. Closed Loop 1
[114]
Ext. Closed Loop 2
[115]
Ext. Closed Loop 3
[139]
Bus ctrl.
[141]
Bus ctrl t.o.
26-41 Terminal X42/7 Min. Scale
Range:
0.00 %*
[0.00 - 200.00 %]
26-42 Terminal X42/7 Max. Scale
Range:
100.00 %*
[0.00 - 200.00 %]
See principle graph for par. 6-52
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Set the function of terminal X42/7 as an analog voltage output.
: 0 - 100 Hz, (0-20 mA)
: Minimum reference - Maximum reference, (0-20 mA)
: -200% to +200% of par. 20-14
: 0 - Inverter Max. Current (par. 16-37
: 0 - Torque limit (par. 4-16
: 0 - Motor rated torque, (0-20 mA)
: 0 - Motor rated power, (0-20 mA)
: 0 - Speed High Limit (par. 4-13
Limit [Hz]
), (0-20 mA)
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
: 0 - 100%, (0-20 mA)
Function:
Scale the minimum output of the selected analog signal at terminal X42/7, as a percentage of the
maximum signal level. E.g. if a 0 V (or 0 Hz) is desired at 25% of the maximum output value. Then
programme 25%. Scaling values up to 100% can never be higher than the corresponding setting
in par. 26-42
Terminal X42/7 Max. Scale
See principle graph for par. 6-51
Function:
Scale the maximum output of the selected analog signal at terminal X42/7. Set the value to the
maximum value of the voltage signal output. Scale the output to give a voltage lower than 10V at
full scale; or 10V at an output below 100% of the maximum signal value. If 10V is the desired output
current at a value between 0-100% of the full-scale output, programme the percentage value in the
parameter, i.e. 50% = 10V. If a voltage between 0 and 10V is desired at maximum output, calculate
the percentage as follows:
(
V
10
desired maximum voltage
i.e.
V
10
V
5
:
× 100 % = 200 %
5
V
Terminal 42 Output Max Scale
.
MG.20.W1.22 - VLT is a registered Danfoss trademark
Maximum Reference/Feedb.
, (0-20 mA)
Inv. Max. Current
), (0-20 mA)
Torque Limit Motor Mode
), (0-20 mA)
Motor Speed High Limit [RPM]
and par. 4-14
.
Terminal 42 Output Min Scale
.
)
x
100 %
2 Parameter Description
2
Motor Speed High
259