Danfoss VLT Automation VT Drive FC 322 Programming Manual page 260

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

2 Parameter Description
26-34 Term. X42/5 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
2
26-35 Term. X42/5 High Ref./Feedb. Value
Range:
100.000*
[-999999.999 - 999999.999 ]
26-36 Term. X42/5 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
26-37 Term. X42/5 Live Zero
Option:
[0]
Disabled
[1] *
Enabled
258
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Enter the analog input scaling value that corresponds to the low voltage value set in
Terminal X42/5 Low Voltage
par. 26-30
.
Function:
Enter the analog input scaling value that corresponds to the high voltage value set in
par. 26-21
Terminal X42/3 High Voltage
Function:
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
noise in terminal X42/5. A high time constant value improves dampening but also increases the time
delay through the filter. This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to enable the Live Zero monitoring. E.g. where the analog input
is a part of the frequency converter control, rather than being used as part of a decentral I/O system,
such as a Building Management System.
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
.
Programming Guide