VLT Automation VT Drive FC322
Programming Guide
3-86 Check Valve Ramp End Speed [RPM]
Range:
0 [RPM]*
[0 – Motor Speed Low Limit [RPM]] Set the speed in [RPM] below Motor Speed Low Limit where the Check Valve is expected to be closed
3-87 Check Valve Ramp End Speed [Hz]
Range:
0 [Hz]*
[0 – Motor Speed Low Limit [Hz]]
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
different from 0 seconds, the Check Valve Ramp Time is effectuated and will be used to ramp down
the speed from Motor Speed Low Limit to the Check Valve End Speed in par. 3-86 or par. 3-87.
Function:
and the Check Valve no longer shall be active.
Function:
Set the speed in [Hz] below Motor Speed Low Limit where the Check Valve Ramp will no longer be
active.
MG.20.W1.22 - VLT is a registered Danfoss trademark
2 Parameter Description