Danfoss VLT Automation VT Drive FC 322 Programming Manual page 258

Hide thumbs Also See for VLT Automation VT Drive FC 322:
Table of Contents

Advertisement

2 Parameter Description
26-02 Terminal X42/5 Mode
Option:
2
[1] *
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
26-10 Terminal X42/1 Low Voltage
Range:
0.07 V*
[Application dependant]
26-11 Terminal X42/1 High Voltage
Range:
10.00 V*
[Application dependant]
26-14 Term. X42/1 Low Ref./Feedb. Value
Range:
0.000*
[-999999.999 - 999999.999 ]
26-15 Term. X42/1 High Ref./Feedb. Value
Range:
100.000*
[-999999.999 - 999999.999 ]
26-16 Term. X42/1 Filter Time Constant
Range:
0.001 s*
[0.001 - 10.000 s]
26-17 Term. X42/1 Live Zero
Option:
[0]
Disabled
256
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20772-Danfoss-131X8135-VLT-Automation-VT-Drive-VFD-FC322-230V-5-HP.aspx
Function:
Terminal X42/5 can be programmed as an analog input accepting a voltage or input from either Pt
1000 (1000
at 0 C) or Ni 1000 (1000
Pt 1000, [2] and Ni 1000, [4] if operating in Celsius - Pt 1000, [3] and Ni 1000, [5] if operating in
Fahrenheit.
Notice: If the input is not in use, it must be set for Voltage!
If set for temperature and used as feed back, the unit must be set for either Celsius or Fahrenheit
(par. 20-12
Reference/Feedback Unit
, par. 21-10
Feedback Unit
Ext. 3 Ref./Feedback Unit
or par. 21-50
Function:
Enter the low voltage value. This analog input scaling value should correspond to the low reference/
Term. X42/1 Low Ref./Feedb. Value
feedback value set in par. 26-14
Function:
Enter the high voltage value. This analog input scaling value should correspond to the high refer-
Term. X42/1 High Ref./Feedb. Value
ence/feedback value set in par. 26-15
Function:
Enter the analog input scaling value that corresponds to the low voltage value set in
Terminal X42/1 Low Voltage
par. 26-10
.
Function:
Enter the analog input scaling value that corresponds to the high voltage value set in
Terminal X42/1 High Voltage
par. 26-11
Function:
Enter the time constant. This is a first-order digital low pass filter time constant for suppressing
noise in terminal X42/1. A high time constant value improves dampening but also increases the time
delay through the filter. This parameter cannot be adjusted while the motor is running.
Function:
This parameter makes it possible to enable the Live Zero monitoring. E.g. where the analog input
is a part of the frequency converter control, rather than being used as part of a decentral I/O system,
such as a Building Management System.
MG.20.W1.22 - VLT is a registered Danfoss trademark
VLT Automation VT Drive FC322
at 0 C) temperature sensors. Select the desired mode.
Ext. 1 Ref./Feedback Unit
, par. 21-30
).
.
.
.
Programming Guide
Ext. 2 Ref./