Omron SYSMAC CS Series Operation Manual page 765

Programmable controllers
Hide thumbs Also See for SYSMAC CS Series:
Table of Contents

Advertisement

Auxiliary Area
Address
Name
Words
Bits
A401
A40109
Program
Error Flag
(Fatal error)
A40110
I/O Setting
Error Flag
(Fatal error)
A40111
Too Many
I/O Points
Flag
(Fatal error)
A40112
Inner Board
Stopped
Error Flag
(Fatal error)
A40113
Duplication
Error Flag
(Fatal error)
Function
ON when program contents are incorrect.
CPU Unit operation will stop and the ERR/ALM indica-
tor on the front of the CPU Unit will light. The task
number where the error occurred will be stored in
A294 and the program address will be stored in A298
and A299.
The type of program error that occurred will be stored
in bits 8 to 15 of A295. Refer to the description of A295
or to 2-3 Checking Programs of CS/CJ Series Pro-
grammable Controllers (W394) for more details on
program errors.
1: Error
0: No error
This flag will be turned OFF when the error is cleared.
ON when a Unit in the registered I/O tables does not
agree with the Unit in the real I/O tables (i.e., the Unit
actually connected).
CPU Unit operation will stop and the ERR/ALM indica-
tor on the front of the CPU Unit will light.
1: Error
0: No error
This flag will be turned OFF when the error is cleared.
ON when the number of I/O points being used in Basic
I/O Units exceeds the maximum allowed for the PLC.
CPU Unit operation will stop and the ERR/ALM indica-
tor on the front of the CPU Unit will light.
1: Error
0: No error
This flag will be turned OFF when the error is cleared.
ON when there is an Inner Board Error (Watchdog
timer error).
CPU Unit operation will stop and the ERR/ALM indica-
tor on the front of the CPU Unit will light.
1: Error
0: No error
This flag will be turned OFF when the error is cleared,
but will be turned ON again unless the cause of the
error is eliminated.
ON in the following cases:
• Two CPU Bus Units have been assigned the same
unit number.
• Two Special I/O Units have been assigned the same
unit number.
• Two Basic I/O Units have been allocated the same
data area words.
CPU Unit operation will stop and the ERR/ALM indica-
tor on the front of the CPU Unit will light.
The duplicated unit number is indicated in A409 to
A416.
1: Duplication error
0: No duplication
(This flag will be turned OFF when the error is
cleared.)
Appendix B
Status
Status at
Write timing/
after
startup
Related flags,
mode
change
Cleared
Cleared
A294,A295, A298 and
A299
Cleared
Cleared
A40508
Cleared
Cleared
A407
Cleared
Cleared
---
Cleared
Cleared
A410 to A416
settings
727