B7A Interface Units
Function Setting Switch
Display
Name
15IN +
Input mode set-
ERR
ting
Set functionality using the DIP switch on the back of the Unit.
OFF
ON
CS1W-B7A12
Pin
Name
1
Transmission delay
2
Transmission error process
3
Input mode
4
ERROR 1 indicator enable
5
ERROR 2 indicator enable
6
Not used. (Leave OFF.)
Defaults: Pins 4 and 5 are turned ON and all other pins are turned OFF.
CS1W-B7A02
Pin
Name
1
Transmission delay
2 to 6 Not used. (Leave OFF.)
Defaults: All pins are turned OFF
CS1W-B7A21
Pin
Name
1
Transmission delay
2
Transmission error process
3
Input mode
5
ERROR indicator enable
4, 6
Not used. (Leave OFF.)
Defaults: Pin 5 is turned ON and all other pins are turned OFF
Color
Status
Orange
ON
The input mode is set to 15
inputs + error input.
OFF
The input mode is set to 16
inputs.
OFF
Standard (19.2 ms)
Hold status
16 inputs
Disabled
Disabled
NA
OFF
Standard (19.2 ms)
NA
OFF
Standard (19.2 ms)
Hold status
16 inputs
Disabled
NA
Section 3-8
Condition
ON
High-speed (3 ms)
Reset Inputs
15 inputs + error input
Enabled
Enabled
NA
ON
High-speed (3 ms)
NA
ON
High-speed (3 ms)
Reset Inputs
15 inputs + error input
Enabled
NA
247